The SM1B series is a new generation of manual starters with thermal and
magnetic trip releases. Motor control and protection, up to 20HP at 460V,
are possible by the choice of suitable adjustment range, 0.1 to 32A. A magnetic
trip indicator integrated on the SM1B starters avoids dangerous closing operations
during short-circuit conditions, previously disconnected by the starter.
The SM1B types are suitable for isolation.

Operational characteristics

– Rated insulation voltage Ui: 690V
– Rated impulse voltage: 6kV
– Rated frequency: 50/60Hz
– Maximum rated current: 32A
– Number of adjustment ranges: 15 (0.1 to 32A)
– Power dissipation per phase: 2.2-9.7W
– Magnetic tripping: 12 In max
– Thermal tripping time class: 10A
– Single-phase sensitive
– Mechanical life: 100,000 cycles
– Electrical life 32A (AC3): 100,000 cycles
– Utilization category: A
– Mounting on 35mm DIN rail (IEC/EN 60715)
– Mounting position: any
– Degree of protection: IP20.

Certifications and compliance
UL listed, for USA and Canada, file E93602.
Compliant with standards: IEC/EN 60947-1,
IEC/EN 60947-2, IEC/EN 60947-4-1.


Thermal Trip rangeMaximum Horsepower RatingsPart Number
PDF File
Single PhaseThree phase
120v240v200v240v480v600v
[A][HP][HP][HP][HP][HP][HP]
0.1-0.16------11SM1B00
0.16-0.25------11SM1B04
0.25-0.4------11SM1B08
0.4-0.63------11SM1B12
0.63-1----1/21/211SM1B16
1-1.6-1/10--3/4111SM1B20
1.6-2.5-1/6-1/211 1/211SM1B24
2.5-41/81/31/23/42311SM1B28
4-6.51/41/23/41 1/23511SM1B32
6.3-101/21 1/21 1/2357 1/211SM1B36
9-143/4223101011SM1B40
13-181355101511SM1B44
17-231 1/2357 1/2152011SM1B48
20-25237 1/27 1/2152011SM1B52
24-32251010203011SM1B56